  • Improved to increase airflow for easier opening and closing
  • Protects from structural damage because of temperature/pressure build up
  • Compensates for air expansion and contraction
  • Heated model available for freezer applications
  • Material: Body - All metal parts are aluminium. Internal sleeve - self-extinguishing Lexan
  • UL Listing: File No. E57306
  • Diameter: See ordering information
  • Length: Standard for 101.6mm (4") wall thickness; other lengths available. Specify exact wall thickness; we will convert to our part number
  • Mounting: May be mounted through wall or ceiling. Drilled for 4.0mm (No. 8) screws
  • Electrical Requirements: See ordering information
Product Code Description
1830000004 Heated Vent, 23W, 0.2A @ 115VAC
1830000008 Heated Vent, 23W, 0.1A @ 220VAC
1830000016 Heated Vent, 20W, 0.8A @ 24VAC

NOTE: These ventilators are for a 101.6mm (4") thick wall. When other length is required, specify exact wall thickness. We will convert your individual requirement into our part number

1825 / 1830 Series Ventilator Quantity Selector
Size of Cooler
(ft)
Volume of Cooler
(cubic ft)
Number of Ventilators Required
-17.8°C to -12.2°C
(0°F to 10°F)
-34°C to -17.8°C
(-30°F to 0°F)
1830 1832 1830 1832
5x5x7 175 1 1 1 1
10x10x7 700 1 1 1 1
15x15x7 1575 1 1 1 1
20x20x7 2800 1 1 2 1
25x25x7 4375 2 1 3 2
30x30x7 6300 2 1 3 2
35x35x7 8575 2 1 3 2
40x40x7 11200 3 2 4 2
45x45x7 14175 3 2 4 2
50x50x7 17500 4 2 5 3
55x55x7 21175 4 2 6 3
60x60x7 25200 5 3 7 4
Performance Test of 1830 Heated Vent vs 1832 Hi-Flow Heated Vent